78
YORK INTERNATIONAL
OPERATING WEIGHTS COPPER FIN COILS
ISOLATOR
MAX LOAD DEFL.
TYPE & SIZE
lbs. kg in. mm
AWMR-1-53 1000 453.6 2 51
AWMR-1-530 1150 521.6 2 51
AWMR-1-531 1276 578.8 2 51
AWMR-1-532 1500 680.4 2 51
AWMR-1-551 1676 760.2 2 51
AWMR-1-552 1900 861.8 2 51
AWMR-1-553 2200 997.9 2 51
AWMR-2-531 2552 1157.6 2 51
AWMR-2-532 3000 1360.8 2 51
COPPER FIN COIL WEIGHT DISTRIBUTION BY MODEL ( KGS )
YCAS A B C D E F G H I J K L M N O P TOTAL
0373 764 691 861 –– 607 745 899 ––         4,567
0403 777 700 880 –– 627 757 928 ––         4,668
0453 782 708 883 –– 614 754 908 ––         4,649
0503 794 717 901 –– 633 767 937 ––         4,750
0543 796 633 784 589 877 615 754 697         5,745
0573 803 640 794 591 867 612 748 689         5,744
0623 814 646 803 599 884 621 762 702         5,831
0653 901 732 1060 499 960 681 1147 514         6,494
Technical Data
INSTALLATION INSTRUCTIONS FOR VMC SERIES AWR/AWMR
AND CP RESTRAINED MOUNTINGS
1. Floor should be level and smooth.
2. For indoor applications, isolators do not normally
require bolting. If necessary, anchor isolators to floor
through bolt holes in base plate. IMPORTANT:
Isolators must be bolted to substructure and
equipment to isolators when used under out-
door equipment exposed to wind forces.
3. Lubricate threads of adjusting bolt. Loosen hold-
down bolts to allow for isolator adjustment.
4. Block the equipment 1/4" higher than the specified
free height of the isolator. To use the isolator as
blocking for the equipment, insert a 1/4" shim be-
tween the upper load plate and vertical uprights.
Lower the equipment on the blocking or shimmed
isolators.
5. Complete piping and fill equipment with water, re-
frigerant, etc.
6. Turn leveling bolt of first isolator four full revolu-
tions and proceed to mount each in turn.
7. Continue turning leveling bolts until equipment is fully
supported by all mountings and equipment is raised
free of the spacer blocks or shims. Remove blocks
or shims.
8. Turn leveling bolt of all mountings in either direction
in order to level the installation.
9. Tighten nuts on hold down bolts to permit a clear-
ance of 1/8" between resilient washer and under-
side of channel cap plate.
10. Installation is now complete.
ISOLATOR
MAX LOAD DEFL.
SPRING
TYPE & SIZE
lbs. kg in. mm
COLOR
CP-2-26 1200 544.3 1.17 29.7 Purple
CP-2-27 1500 680.4 1.06 26.9 Orange
CP-2-28 1800 816.4 1.02 25.9 Green
CP-2-31 2200 997.9 0.83 21.0 Gray
CP-2-32 2600 1179.3 0.74 18.7 White
CP-2-35 3000 1360.8 0.70 17.7 Gold

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the York MILLENNIUM YCAS0623 and is the answer not in the manual?

York MILLENNIUM YCAS0623 Specifications

General IconGeneral
BrandYork
ModelMILLENNIUM YCAS0623
CategoryChiller
LanguageEnglish

Related product manuals