41
YORK INTERNATIONAL
FORM 201.18-NM2
TEMPERATURES AND FLOWS
NOTES:
1. For leaving brine temperature below 4.4°C, contact your nearest YORK office for application requirements.
2. For leaving water temperature higher than 13°C, contact the nearest YORK office for application guidelines.
3. The evaporator is protected against freeze-up to -28.8°C with an electrical heater as standard.
MODEL LEAVING WATER COOLER FLOW AIR ON
NUMBER
TEMPERATURE (°C) (L/S)
3
CONDENSER (°C)
YCAS MIN.
1
MAX.
2
MIN. MAX. MIN. MAX
0373 4.4 13.0 9.3 37.8 -17.7 51.7
0403 4.4 13.0 10.7 37.8 -17.7 51.7
0453 4.4 13.0 11.5 37.8 -17.7 51.7
0503 4.4 13.0 11.5 37.8 -17.7 51.7
0543 4.4 13.0 12.8 47.1 -17.7 51.7
0573 4.4 13.0 12.8 47.1 -17.7 51.7
0623 4.4 13.0 12.8 47.1 -17.7 51.7
0653 4.4 13.0 12.8 47.1 -17.7 51.7
WATER PRESSURE DROP
FIG. 10 – FLOW RATE AND PRESSURE DROP CHARTS
MODEL NUMBER YCAS COOLER
0373, 0403, 0453, 0503 A
0543, 0573, 0623, 0653 B
7
A
B
100
10
1
1
Water Flow (l/s)
Cooler Water Pressure Drop
A = 0.1737 (l/s)^1.82
B = 0.1393 (l/s)^1.80
10
100
1000
Pressure Drop (kPa)
LD05121