17
JOHNSON CONTROLS
FORM 201.21-NM1 (1223)
2
Display
The display consists of a liquid crystal 2 line by 40
characters per line display, with backlighting for outdoor
viewing of operating parameters and program points.
Parameters are displayed in 5 languages in either Eng-
lish (°F and PSIG) or Metric (°C and Bars) units, and for
each circuit, the following items can be displayed:
Entering and leaving chilled liquid, and ambient
temperature.
Day, date and time. Daily start/stop times. Holiday
and Manual Override status.
Compressor operating hours and starts. Automatic or
manual lead/lag. Lead compressor identication.
Run permissive status. Compressor run status.
Anti-recycle timers.
System suction (and suction superheat), discharge
(and discharge superheat), and oil pressures and
temperatures.
Percent full load compressor motor current and
average motor current. Compressor motor speed
(frequency).
Cutout status and setpoints for: supply chilled liquid
temperature, low suction pressure, high discharge
pressure and temperature, high oil temperature, low
ambient, and low leaving liquid temperature.
Unloading limit setpoints for high discharge pres-
sure and compressor motor current.
Status of: evaporator heater, condenser fans, load/
unload timers, and chilled water pump.
“Out of range” message.
Up to 10 fault shutdown histories.
Keypad
An operator keypad allows complete control of the
system from a central location. The keypad utilizes
an overlay to allow use in 5 languages. The keypad is
a color-coded, 36 button, sealed keypad with keys for
Display, Entry, Setpoints, Clock, Print, Program, Unit
ON/OFF and other functions. Details on a few of the
keys follow.
Status – Allows viewing present unit or system status
displayed by the microprocessor.
Entry – Numeric keypad and supporting keys used to
conrm Setpoint changes, cancel inputs, advance day,
and change AM/PM.
Setpoints – For setting chilled liquid temperature,
chilled liquid range, remote reset temperature range.
Date/Time – Used to set time, daily or holiday start/stop
schedule, manual override for servicing, and sound
limiting schedule.
Print – Used to display or print operating data or sys-
tem fault shutdown history for last ten faults. Printouts
are generated through an RS-232 port via a separate
printer.
Program – For setting low leaving liquid temperature
cutout, average motor current limit, and pulldown de-
mand limit.
Displays are also provided for programming low am-
bient cutout, low suction pressure cutout, superheat
setpoint, etc., under the PROGRAM key.
Unit Switch
A master unit switch allows activation or de-activation
of the chiller system. Separate system switches for con-
trolling each system are provided as part of the chiller
control panel keypad.