261
JOHNSON CONTROLS
FORM 201.21-NM1 (1223)
8
MOTOR TMP XXX.X XXX.X XXX.X DEGF
COMPRESSOR SPEED XXX.X%
LIQUID LINE SOLENOID O N
FLASH TANK LEVEL XXX.X %
FEED VALVE % OPEN XXX.X %
DRAIN VALVE % OPEN XXX.X %
CONDENSER FANS ON 3
COMPRESSOR HEATER OFF
RUN PERMISSIVE O N
VSD RUN RELAY O F F
VSD SOFTWARE RUN SIGNAL O F F
UNIT OPERATING SCHEDULE
S M T W T F S *=HOLIDAY
MON START=00:00AM STOP=00:00AM
TUE START=00:00AM STOP=00:00AM
WED START=00:00AM STOP=00:00AM
THU START=00:00AM STOP=00:00AM
FRI START=00:00AM STOP=00:00AM
SAT START=00:00AM STOP=00:00AM
HOL START=00:00AM STOP=00:00AM
SOUND LIMIT SCHEDULE
(This section is printed only if the sound limit
schedule is enabled)
MON START=00:00AM STOP=00:00AM
TUE START=00:00AM STOP=00:00AM
WED START=00:00AM STOP=00:00AM
THU START=00:00AM STOP=00:00AM
FRI START=00:00AM STOP=00:00AM
SAT START=00:00AM STOP=00:00AM
HOL START=00:00AM STOP=00:00AM
HISTORY DATA PRINTOUT
History printouts, when selected, provide stored data
relating to all specic system and chiller operating
conditions at the time of the fault, regardless of whether
a lockout occurred. History information is stored in
battery-backed memory on the Chiller Control Board
and is not aected by power failures or resetting of
faults. Whenever a fault of any type occurs, all system
operating data is stored in battery-backed memory at
the instant of the fault. The history printout is similar
to the operating data printout except for the change in
the header information shown below:
YORK INTERNATIONAL CORPORATION
LATITUDE SCREW CHILLER
HISTORY NUMBER 1
2:04:14 PM 18 JUN 04
SYS 1 YYYYYYY
HIGH DSCH PRESS SHUTDOWN
STATUS AT TIME OF SHUTDOWN
SYS 1 XXXXXXXXXXXXXXXXXXXXXXXXXX
SYS 2 XXXXXXXXXXXXXXXXXXXXXXXXXX
ALL FAULTS
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
The most recent fault will always be stored as HISTORY
BUFFER #1.
PRINT KEY (CON'T)