ELECTRICAL NOTES
1. As standard, all units have single point power connection. Contact factory for information regarding dual point power units.
2. Maximum Inverse Time Circuit Breaker - 250% of the rated input current of the drive per NEC 430.52 (C1).
3. Maximum Dual Element (Time Delay) Fuse - 225% of the rated input current of the drive per NEC 430.52 (C1).
4. MCA - Minimum Circuit Ampacity - 125% of the largest compressor RLA plus 100% of the remaining compressor RLA’s plus the sum of all
condenser fan FLA’s per NEC 440.33
5. Recommended time delay or dual element fuse size - 150%of the largest compressor RLA plus 100% of the remaining compressor RLA’s
plus the sum of all condenser fan FLA’s.
6. RLA - Rated Load Amps - rated in accordance with UL standard 1995.
7. Local codes may take precedence.
8. Control KVA includes operational controls and evaporator heaters.
9. System inrush current is less than RLA due to the use of YORK Variable Speed Drive technology. Typical Compressor Starting Current
( .rst four seconds of startup):
Rated Voltage Typical Starting Current per Compressor
200/60/3 53A
230/60/3 46A
380/60/3 29A
460/60/3 23A
575/60/3 18A
10. Optional Compressor Service Disconnect switch is available on all units.
11. Voltage Utilization Range:
Rated Voltage Utilization Range
200/60/3 180-220
230/60/3 208-254
380/60/3 342-402
460/60/3 414-508
575/60/3 520-635
12. Condenser fan FLA applies to both low sound and ultra quiet fans.
LEGEND:
C.B. CIRCUIT BREAKER
D.E. DUAL ELEMENT FUSE
DISC SW DISCONNECT SWITCH
FACT CB FACTORY-MOUNTED CIRCUIT BREAKER
FLA FULL LOAD AMPS
HZ HERTZ
MAX MAXIMUM
MCA MINIMUM CIRCUIT AMPACITY
MIN MINIMUM
MIN NF MINIMUM NON-FUSED
RLA RATED LOAD AMPS
S.P. WIRE SINGLE-POINT WIRING
NOTES:
1. U.L. Label is provided on 60 Hz units for these electrical wiring congurations.
2. –– –– –– –– –– –– Dashed Line = Field Provided Wiring.
3. The above recommendations are based on the National Electric Code and using copper conductors only. Field wiring must also comply with local codes.
Group Rated breaker must be HACR type for cUL machines.
TECHNICAL DATA