2020
YHVP-ECM
YHVP-ECM Serie
20
EUROVENT certifications
(E) = Eurovent certied performance. MIN-MED-MAX = Standard connected speeds.
(*) = The sound pressure levels are 9 dB(A) lower than the sound power levels and apply to the reverberant eld of a 100 m
3
room
and a reverberation time of 0.5 sec.
Technical features
MODEL YHVP-ECM 1 YHVP-ECM 2
Inverter power
1 (E) 3 5 (E) 7,5 10 (E) 1 (E) 3 5 (E) 7,5 10 (E)
MIN MED MAX MIN MED MAX
Air ow m
3
/h
190 240 290 355 415 260 315 375 440 510
Cooling total emission (E) kW
1,17 1,39 1,58 1,81 2,00 1,47 1,67 1,87 2,07 2,26
Cooling sensible emission (E) kW
0,86 1,04 1,20 1,40 1,57 1,10 1,28 1,46 1,64 1,83
Heating (E) kW
1,50 1,82 2,12 2,48 2,78 1,94 2,25 2,58 2,90 3,23
ΔP Cooling (E) kPa
5,0 6,3 7,7 9,5 11,2 6,9 8,4 10,1 11,8 13,7
ΔP Heating (E) kPa
4,2 5,4 6,5 8,2 9,3 5,6 6,9 8,5 9,7 11,6
Fan (E) W
6 7 9 11 15 7 9 12 16 21
Sound power (E) Lw dB(A)
35 39 46 48 52 40 44 47 51 55
Sound pressure (*) Lp dB(A)
26 30 37 39 43 31 35 38 42 46
MODEL YHVP-ECM 3 YHVP-ECM 4
Inverter power
1 (E) 3 5 (E) 7,5 10 (E) 1 (E) 3 5 (E) 7,5 10 (E)
MIN MED MAX MIN MED MAX
Air ow m
3
/h
270 345 420 520 620 375 465 550 665 770
Cooling total emission (E) kW
1,83 2,20 2,53 2,93 3,29 2,34 2,72 3,05 3,43 3,75
Cooling sensible emission (E) kW
1,31 1,60 1,86 2,19 2,50 1,70 2,01 2,29 2,63 2,92
Heating (E) kW
2,20 2,69 3,15 3,72 4,25 2,87 3,41 3,88 4,48 4,99
ΔP Cooling (E) kPa
10,7 14,8 19,0 24,8 30,4 16,5 21,6 26,6 32,9 38,7
ΔP Heating (E) kPa
8,5 11,7 15,1 19,9 24,2 12,6 17,2 21,2 26,6 31,4
Fan (E) W
6 8 11 15 20 9 12 16 22 30
Sound power (E) Lw dB(A)
37 42 45 49 53 43 46 49 53 57
Sound pressure (*) Lp dB(A)
28 33 36 40 44 34 37 40 44 48
www.eurovent-certification.com
www.certiflash.com
COOLING (summer operation)
Entering air temperature: + 27°C d.b. / + 19°C w.b.
Water temperature: + 7°C E.W.T. / + 12°C L.W.T.
HEATING (winter operation)
Entering air temperature: + 20°C
Water temperature: + 50°C E.W.T.
Water ow rate as for the cooling conditions
2-pipe units
The following standard rating conditions are used: