6
YHVP
YHVP
Serie
6
EUROVENT certifications
(E) = Eurovent certied performance. MIN-MED-MAX = Standard connected speeds.
(*) = The sound pressure levels are 9 dB(A) lower than the sound power levels and apply to the reverberant eld of a 100 m
3
room
and a reverberation time of 0.5 sec.
Technical features
MODEL
YHVP 1 YHVP 2
Speed
1 (E) 2 (E) 3 4 (E) 5 6 1 (E) 2 3 (E) 4 5 (E) 6
MIN MED MAX MIN MED MAX
Air ow m
3
/h
205 270 340 375 470 500 250 305 365 400 480 545
Cooling total emission (E) kW
1,24 1,50 1,76 1,87 2,15 2,23 1,43 1,63 1,84 1,95 2,18 2,35
Cooling sensible emission (E) kW
0,92 1,14 1,36 1,46 1,72 1,80 1,07 1,25 1,43 1,53 1,75 1,92
Heating (E) kW
1,60 2,00 2,39 2,58 3,04 3,17 1,88 2,20 2,39 2,70 3,09 3,38
ΔP Cooling (E) kPa
4,8 6,8 9,0 10,1 13,0 13,9 6,2 7,9 9,8 10,9 13,3 15,2
ΔP Heating (E) kPa
3,7 5,5 7,2 8,3 10,6 10,8 4,8 6,4 7,2 8,5 10,9 12,5
Fan (E) W
12 14 17 18 24 30 12 14 18 20 24 32
Sound power (E) Lw dB(A)
35 41 46 48 52 53 39 43 47 49 53 55
Sound pressure (*) Lp dB(A)
26 32 37 39 43 44 30 34 38 40 44 46
MODEL
YHVP 3 YHVP 4
Speed
1 (E) 2 (E) 3 4 (E) 5 6 1 2 (E) 3 4 (E) 5 6 (E)
MIN MED MAX MIN MED MAX
Air ow m
3
/h
280 375 480 545 730 780 300 440 500 610 675 790
Cooling total emission (E) kW
1,89 2,32 2,78 3,03 3,63 3,78 1,99 2,62 2,86 3,26 3,46 3,81
Cooling sensible emission (E) kW
1,35 1,69 2,06 2,27 2,81 2,95 1,43 1,93 2,12 2,47 2,66 2,98
Heating (E) kW
2,26 2,84 3,49 3,86 4,79 5,03 2,40 3,26 3,61 4,20 4,53 5,07
ΔP Cooling (E) kPa
11,2 16,2 22,5 26,2 36,4 39,1 12,3 20,2 23,6 29,9 33,4 39,7
ΔP Heating (E) kPa
8,7 12,6 17,7 21,2 29,3 31,9 9,7 15,9 19,1 23,7 27,2 31,5
Fan (E) W
16 21 26 29 38 46 17 23 27 32 35 48
Sound power (E) Lw dB(A)
35 40 45 48 55 57 36 43 46 51 54 57
Sound pressure (*) Lp dB(A)
26 31 36 39 46 48 27 34 37 42 45 48
www.eurovent-certification.com
www.certiflash.com
COOLING (summer operation)
Entering air temperature: + 27°C d.b. / + 19°C w.b.
Water temperature: + 7°C E.W.T. / + 12°C L.W.T.
HEATING (winter operation)
Entering air temperature: + 20°C
Water temperature: + 50°C E.W.T.
Water ow rate as for the cooling conditions
2-pipe units
The following standard rating conditions are used: