Communication with Modbus
A43/A44 152 2CMC48001M0201
User Manual Revision: C
second register holds the number of the output to set, in case Set output action
is used.
Set bit in alarm register
output bit above is set to 0.
Note – Both registers in the table above must be written in one operation, otherwise
the value will not take effect.
Write alarm configuration
Follow the steps in the table below to configure the parameters for monitoring
the value of a number of quantities in the meter:
Write the number of the alarm to configure to the Alarm number register. This
is a value between 1 and 25.
Write the OBIS code for the quantity to monitor to the Quantity registers.
Write the ON and OFF thresholds to the Thresholds registers.
Write the ON and OFF delays to the Delays registers.
Write the actions to perform to perform to the Action registers.
Repeat step 1 to 4 for all alarms that shall be used.
Follow the steps in the table below to read the current configuration of monitoring
Write the number of the alarm to read configuration for to the Alarm number
register. This is a value between 1 and 25.
Read the Quantity registers to get the quantity monitored in the chosen alarm.
Read the Thresholds registers to get the ON and OFF thresholds.
Read the Delays registers to get the ON and OFF delays.
Read the Action registers to get the actions performed when an alarm is