Communication with M-Bus
A43/A44 276 2CMC48001M0201
User Manual Revision: C
10.5.4 Reset power fail counter
The power fail counter is reset to 0 by sending the following command (all values
are hexadecimal). The command is not affected by the write protection level set.
L-field, calculated from C field to last user data
CI-field, data send, LSB first
VIF next byte is manufacturer specific
CS checksum, calculated from C field to last data
10.5.5 Set Current transformer (CT) ratio - primary current
The current transformer ratio (CT) primary current is set by sending the
following command (all values are hexadecimal). The command is affected by
the write protection level set.
L-field, calculated from C field to last user data
CI-field, data send, LSB first
VIF next byte is manufacturer specific
VIFE CT ratio primary current
New CT ratio primary current
CS checksum, calculated from C field to last data