Fault tracing
109
F0016 EARTH FAULT
(programmable
fault function 3017)
Drive has detected earth (ground)
fault in motor or motor cable.
Check motor.
Check fault function parameter setting.
Check motor cable. Motor cable length must not
exceed maximum specifications. See section Motor
connection on page 119.
F0017 UNDERLOAD
(programmable
fault function
3013...3015)
Motor load is too low due to e.g.
release mechanism in driven
equipment.
Check for problem in driven equipment.
Check fault function parameter settings.
Check motor power against unit power.
F0018 THERM FAIL Drive internal fault. Thermistor
used for drive internal temperature
measurement is open or
short-circuited.
Contact your local ABB representative.
F0021 CURR MEAS Drive internal fault. Current
measurement is out of range.
Contact your local ABB representative.
F0022 INPUT PHASE
LOSS
(programmable
fault function 3016)
Intermediate circuit DC voltage is
oscillating due to missing input
power line phase or blown fuse.
Fault trip occurs when DC voltage
ripple exceeds 14% of nominal DC
voltage.
Check input power line fuses.
Check for input power supply imbalance.
Check fault function parameter setting.
F0026 DRIVE ID Internal drive ID fault Contact your local ABB representative.
F0027 CONFIG FILE Internal configuration file error Contact your local ABB representative.
F0035 OUTP WIRING
(programmable
fault function 3023)
Incorrect input power and motor
cable connection (i.e. input power
cable is connected to drive motor
connection).
Check input power connections.
Check fault function parameter setting.
F0036 INCOMPATIBLE
SW
Loaded software is not
compatible.
Contact your local ABB representative.
F0101 SERF CORRUPT Corrupted Serial Flash chip file
system
Contact your local ABB representative.
F0103 SERF MACRO Active macro file missing from
Serial Flash chip
Contact your local ABB representative.
F0201 DSP T1
OVERLOAD
System error
Contact your local ABB representative.
F0202 DSP T2
OVERLOAD
F0203 DSP T3
OVERLOAD
F0204 DSP STACK
ERROR
F0206 MMIO ID ERROR Internal I/O Control board (MMIO)
fault
Contact your local ABB representative.
F1000 PAR HZRPM Incorrect speed/frequency limit
parameter setting
Check parameter settings. Following must apply:
2007 < 2008,
2007/9907 and 2008/9907 are within range.
F1003 PAR AI SCALE Incorrect analog input AI signal
scaling
Check parameter group 13 ANALOG INPUTS
settings. Following must apply:
1301 < 1302.
CODE FAULT CAUSE WHAT TO DO

Table of Contents

Other manuals for ABB ACS150

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB ACS150 and is the answer not in the manual?

ABB ACS150 Specifications

General IconGeneral
Power Range0.37 to 4 kW
Voltage Range200 to 240 V, 380 to 480 V
Frequency50/60 Hz
Control MethodScalar control
Protection ClassIP20
Frequency Range0 to 500 Hz
Storage Temperature-40 to +70 °C
Relative Humidity5 to 95 % (non-condensing)
Ambient Temperature-10 to +50 °C
I/ODigital inputs, Analog inputs, Relay outputs
Overload Capacity150% for 60 seconds
Braking ChopperBuilt-in (for some models)