Control panel
54
How to select the monitored signals
6. Use keys and to select the parameter value. When you have
changed the parameter value, starts flashing.
To save the displayed parameter value, press .
To cancel the new value and keep the original, press .
Step Action Display
1. You can select which signals are monitored in the Output mode and how
they are displayed with group 34 PANEL DISPLAY parameters. See page
53 for detailed instructions on changing parameter values.
By default, you can monitor the following three signals by browsing: 0103
OUTPUT FREQ, 0104 CURRENT and 0105 TORQUE.
To change the default signals, select from group 01 OPERATING DATA up
to three signals to be browsed.
Signal 1: Change the value of parameter 3401 SIGNAL1 PARAM to the
index of the signal parameter in group 01 OPERATING DATA (= number of
the parameter without the leading zero), e.g. 105 means parameter 0105
TORQUE. Value 0 means that no signal is displayed.
Repeat for signals 2 (3408 SIGNAL2 PARAM) and 3 (3415 SIGNAL3
PARAM). For example, if 3401 = 0 and 3415 = 0, browsing is disabled and
only the signal specified by 3408 appears in the display. If all three
parameters are set to 0, i.e. no signals are selected for monitoring, the
panel displays text “n.A.”.
2. Select how you want the signals to be displayed. For details, see
parameter 3404.
Signal 1: parameter 3404 OUTPUT1 DSP FORM
Signal 2: parameter 3411 OUTPUT2 DSP FORM
Signal 3: parameter 3418 OUTPUT3 DSP FORM.
3. Select the units to be displayed for the signals. This has no effect if
parameter 3404/3411/3418 is set to 9 (DIRECT). For details, see
parameter 3405.
Signal 1: parameter 3405 OUTPUT1 UNIT
Signal 2: parameter 3412 OUTPUT2 UNIT
Signal 3: parameter 3419 OUTPUT3 UNIT.
4. Select the scalings for the signals by specifying the minimum and
maximum display values. This has no effect if parameter 3404/3411/3418 is
set to 9 (DIRECT). For details, see parameters 3406 and 3407.
Signal 1: parameters 3406 OUTPUT1 MIN and
3407 OUTPUT1 MAX
Signal 2: parameters 3413 OUTPUT2 MIN and 3414 OUTPUT2 MAX
Signal 3: parameters 3420 OUTPUT3 MIN and 3421 OUTPUT3 MAX.
Step Action Display
SET
LOC
Hz
PAR SET FWD
120
.
LOC
PAR FWD
1203
LOC
PAR SET FWD
103
LOC
PAR SET FWD
104
LOC
PAR SET FWD
105
LOC
PAR SET FWD
9
LOC
PAR SET FWD
3
LOC
Hz
PAR SET FWD
00
.
LOC
Hz
PAR SET FWD
5000
.

Table of Contents

Other manuals for ABB ACS150

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB ACS150 and is the answer not in the manual?

ABB ACS150 Specifications

General IconGeneral
BrandABB
ModelACS150
CategoryController
LanguageEnglish

Related product manuals