108 Technical data
1) These values are not calculated according to the ecodesign standard IEC 61800-9-2.
Symbols
Sizing
The current ratings are the same regardless of the supply voltage within one voltage
range. To achieve the rated motor power given in the table, the rated current of the
drive must be higher than or equal to the rated motor current.
Note 1:
The maximum allowed motor shaft power is limited to 1.5 ·
P
hd
,
1.1 ·
P
N
or
P
cont.max
(whichever value is greatest)
.
If the limit is exceeded, motor torque and
current are automatically restricted. The function protects the input bridge of the
drive against overload. If the condition exists for 5 minutes, the limit is set to
P
cont.max
.
Note 2: The ratings apply at an ambient temperature of 40 °C (104 °F). At lower
temperatures the ratings are higher (except
I
max
).
Note 3: Use the DriveSize PC tool for a more accurate dimensioning if the ambient
temperature is below 40 °C (104 °F) or the drive is loaded cyclically.
Three-phase supply voltage 525 V, 550 V, 575 V, 600 V, 660 V or 690 V
-0011-7 13 14 11 11.5 7.5 8.5 5.5 R4 103 300
-0016-7 1719151511117.5 R4103340
-0020-7 222818.520151511 R4103440
-0025-7 25 38 22 23 18.5 19 15 R4 103 530
-0030-7 33443030222218.5 R4103610
-0040-7 36 54 30 34 30 27 22 R4 103 690
-0050-7 51 68 45 46 37 34 30 R5 250 840
-0060-7 57 84 55 52 45 42 37 R5 250 1010
-0070-7 79 104 75 73 55 54 45 R6 405 1220
-0100-7 93 124 90 86 75 62 55 R6 405 1650
-0120-7 113 172 110 108 90 86 75 R6 405 1960
-0145-7 134 190 132 125 110 95 90 R6 405 2660
-0175-7 166 245 160 155 132 131 110 R6 405 3470
-0205-7 190 245 160 180 160 147 132 R6 405 4180
0009693
Nominal ratings
I
cont.max
continuous rms output current. No overload capability at 40 °C (104 °F).
I
max
maximum output current. Available for 10 s at start, otherwise as long as allowed by
drive temperature.
Typical ratings:
No-overload use
P
cont.max
typical motor power. The power ratings apply to most IEC 60034 motors at the
nominal voltage, 230 V, 400 V, 500 V or 690 V.
Light-overload use (10% overload capability)
I
2N
continuous rms current. 10% overload is allowed for one minute every 5 minutes.
P
N
typical motor power. The power ratings apply to most IEC 60034 motors at the
nominal voltage, 230 V, 400 V, 500 V or 690 V.
Heavy-duty use (50% overload capability)
I
2hd
continuous rms current. 50% overload is allowed for one minute every 5 minutes.
P
hd
typical motor power. The power ratings apply to most IEC 60034 motors at the
nominal voltage, 230 V, 400 V, 500 V or 690 V.
ACS800-01
size
Nominal
ratings
No-
overload
use
Light-overload
use
Heavy-duty use Frame
size
Air flow Heat dis-
sipation
(1
I
cont.max
A
I
max
A
P
cont.max
kW
I
2N
A
P
N
kW
I
2hd
A
P
hd
kW
m
3
/h
W