68 Electrical installation
Cabinet installation (IP21, UL type 1)
You can install the drive in a cabinet without the connection box and front cover.
ABB recommends:
Ground the cable shield 360 degrees at the cabinet entry.
Lead the cable unstripped as close to the terminals as possible.
Secure the cables mechanically.
Protect the RMIO board terminals X25 to X27 against contact when input voltage
exceeds 50 V AC.
Frame size R5
Cover the power cable terminals as follows:
1. Cut holes for the installed cables into the clear plastic shroud.
2. Press the shroud onto the terminals.
Removal of the shroud with a screw driver:
1
2
2