Technical data 117
Cable types
The table below gives copper and aluminum cable types for different load currents.
Cable sizing is based on max. 9 cables laid on a cable ladder side by side, ambient
temperature 30 °C (86 °F), PVC insulation, surface temperature 70 °C (158 °F)
(EN 60204-1 and IEC 60364-5-52:2001). For other conditions, size the cables
according to local safety regulations, appropriate input voltage and the load current
of the drive.
Copper cables with
concentric copper shield
Aluminum cables with
concentric copper shield
Max. load
current
A
Cable type
mm
2
Max. load
current
A
Cable type
mm
2
13 3×1.5 61 3×25
18 3×2.5 69 3×35
24 3×4 83 50
30 3×6 107 3×70
42 3×10 130 3×95
56 3×16 151 3×120
71 3×25 174 3×150
88 3×35 199 3×185
107 3×50 235 3×240
137 3×70 274 3 × (3×50) *
167 3×95 260 2 × (3×95) *
193 3×120
223 3×150
255 3×185
301 3×240
3BFA 01051905
* This cable type cannot be used in this drive because the cable
lug is not designed for multiple wires.

Table of Contents

Other manuals for ABB ACS800-U1

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB ACS800-U1 and is the answer not in the manual?

ABB ACS800-U1 Specifications

General IconGeneral
BrandABB
ModelACS800-U1
CategoryController
LanguageEnglish

Related product manuals