Planning the electrical installation 43
Supply connection
Disconnecting device
Install a hand-operated input disconnecting device between the AC power source
and the drive. The disconnecting device must be of a type that can be locked to the
open position for installation and maintenance work.
EU
To meet the European Union Directives, according to standard EN 60204-1, Safety of
Machinery, the disconnecting device must be one of the following types:
Switch-disconnector of utilization category AC-23B (EN 60947-3)
Disconnector that has an auxiliary contact that in all cases causes switching
devices to break the load circuit before the opening of the main contacts of the
disconnector (EN 60947-3)
Circuit breaker suitable for isolation in accordance with EN 60947-2
US
The disconnecting device must conform to the applicable safety regulations.
Fuses
See
Thermal overload and short-circuit protection
(page 44).
Main contactor
If a contactor is used, dimension it according to the nominal voltage and current of
the drive. The utilization category (IEC 947-4) is AC-1.

Table of Contents

Other manuals for ABB ACS800-U1

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB ACS800-U1 and is the answer not in the manual?

ABB ACS800-U1 Specifications

General IconGeneral
BrandABB
ModelACS800-U1
CategoryController
LanguageEnglish

Related product manuals