DescriptionValue or Value range/DefaultProperty/Parameter
Maximum wait time in milli-
seconds within which the first
byte of a link layer response
should have been received.
0 to 65535
Default: 2000
Header Timeout
Specifies whether the link layer
confirmations are in use.
Not In Use
In Use
Default: In Use
Link Layer Confirmations
Enabled
Maximum length of a data
fragment.
50 to 249
Default: 230
Maximum Message Length
Delay in milliseconds between
retransmissions.
0 to 65535
Default: 0
Maximum Random Delay for
Retransmission
Data polling period.0 to 255
Default:10
Polling Period
The time in milliseconds that
DNP3.0 link waits for received
message.
0 to 255
Default: 15
ResponseTimeout
Specifies if 'Test Function for
Link' is enabled.
True
False
Default: False
Test Function for Link
Delay in milliseconds between
test fuction of link commands.
If value is zero (0), the test
function of link command is not
sent.
0 to 65535
Default: 20
Test Function for Link Interval
Configuring DNP LAN Device3.4.4.
Table 3.4.4-1 lists the configurable properties for DNP Devices and value ranges for
these properties. The actual configuration by using Communication Engineering Tool
(CET) is performed as described in 3.4.1, General about configuring objects.
Table 3.4.4-1 DNP LAN IED properties
DescriptionValue or Value range/ DefaultName
Basic
Diagnostics EnabledTrue
False
Default: False
Diagnostics enabled
24
1MRS756566
COM600 Station Automation Series
DNP 3.0
LAN/WAN Master
(OPC) 3.2
User's Guide

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB COM600 Station Automation Series and is the answer not in the manual?

ABB COM600 Station Automation Series Specifications

General IconGeneral
BrandABB
ModelCOM600 Station Automation Series
CategoryController
LanguageEnglish

Related product manuals