Controllable double point (DPC)3.4.8.9.
Table 3.4.8.9-1 Configurable DPC properties for OPC client
DescriptionValue or Value range/ DefaultProperty/ Para-
meter
Basic
Common data class according to IEC
61850.
DPCCommon Data
Class
Addresses
Index for Control Close command.-1 to 65535
Default: -1
Control Index Close
Index for Control Open command.-1 to 65535
Default: -1
Control Index Open
Index for 52a.-1 to 65535
Default: 11
Index 52a
Index for 52b.-1 to 65535
Default: 12
Index 52b
Index for Breaker Failure Indication.-1 to 65535
Default: 12
Index BFI
Data Class Spe-
cific
Qualifier for control.Momentary
Latched
Pulsed
Default: Momentary
Control Code Quali-
fier
Object number for control.Binary control output block
(12).
Control Object
Variation for control0 to 65535Control Variation
Object number for indication.Binary input (1, 2)
Binary output (10)
Default: Binary input (1, 2)
Indication Object
DNP direct operate of SBO (function code
configuration).
True
False
Default: True
Operate
36
1MRS756566
COM600 Station Automation Series
DNP 3.0
LAN/WAN Master
(OPC) 3.2
User's Guide