Configuring Logical Node properties3.4.6.
Table 3.4.6-1 Configuring Logical Node properties
DescriptionValue or Value range/ DefaultProperty/Parameter
Basic
LLN0
Logical node classLLN0Logical Node Class
GGIO1
Logical node classANCR, ARCO, ATCC, AVCO,
LPHD, CALH, CCGR, CILO,
CPOW, CSWI, GAPC, GGIO,
GSAL, IARC, IHMI, ITCI, ITMI,
MDIF, MHAI, MHAN, MMTR,
MMXN, MMXU, MSQI, MSTA,
PDIF, PDIR, PDIS, PDOP,
PDUP, PFRC, PHAR, PHIZ,
PIOC, PMRI, PMSS, POPF,
PPAM, PSCH, PSEF, PTEF,
PTOC, PTOF, PTOV, PTRC,
PTTR, PTUC, PTUV, PUPF,
PTUF, PVOC, PVPH, PZSU,
RDRE, RADR, RBDR, RDRS,
RBRF, RDIR, RFLO, RPSB,
RREC, RSYN, SARC, SIMG,
SIML, SPDC, XCBR, XSWI,
TCTR, TVTR, YEFN, YLTC,
YPSH, YPTR, ZAXN, ZBAT,
ZBSH, ZCAB, ZCAP, ZCON,
ZGEN, ZGIL, ZLIN, ZMOT,
ZREA, ZRRC, ZSAR, ZTCF,
ZTCR
Default: GGIO
Logical Node Class
Logical node instance number1..2000
1
Logical Node Instance
Prefix for logical nodeDefault: NoneLogical Node Prefix
Configuring data objects for internal OPC data3.4.7.
General about configuring data objects for Internal OPC Data3.4.7.1.
Internal data objects describe internal status information of an OPC server, for example
whether the connection between the OPC Server and the device (IED) is working or not.
When there is need to transfer internal information of an OPC server, i.e. information
that does not originate from a device, to an OPC Client, virtual data objects need to be
created.
27
DNP 3.0
LAN/WAN Master
(OPC) 3.2
COM600 Station Automation Series
1MRS756566