DescriptionValue or Value range/
Default
Property/ Parameter
Indication index.-1 to 65535
Default: -1
Indication Index
Data Class Specific
Qualifier for control.Momentary
Latched
Pulsed
Default: Momentary
Control Code Qualifier
Variation for control0 to 65535Control Variation
Specifies using two-step, select-before-operate
method for issuing control request or not.
Direct Operate
Select Before Operate
Default: Direct Operate
Operate
Scale and Unit
Scale to be used with this type.Default: NoneScale
Complex measured value (CMV)3.4.8.7.
Table 3.4.8.7-1 Configurable CMV properties for OPC client
DescriptionValue or Value range/ DefaultProperty/ Para-
meter
Basic
Common data class according to IEC
61850.
CMVCommon Data
Class
Addresses
Indication index.-1 to 65535
Default: -1
Index
Sub-Type
MV sub-typeSimpleSubtype
Data Class Spe-
cific
Object number for indication.Analog input (30, 32)
Analog output (40)
Default: Analog input (30, 32)
Indication Object
Scale and Unit
33
DNP 3.0
LAN/WAN Master
(OPC) 3.2
COM600 Station Automation Series
1MRS756566
User's Guide

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB COM600 Station Automation Series and is the answer not in the manual?

ABB COM600 Station Automation Series Specifications

General IconGeneral
BrandABB
ModelCOM600 Station Automation Series
CategoryController
LanguageEnglish

Related product manuals