DescriptionValue or Value range/ DefaultProperty/ Para-
meter
Variation for control.0 to 65535
Default: 2
Control Variation
Object number for indication.Analog input (30, 32)
Analog output (40)
Default: Analog input (30, 32)
Indication Object
Scale and Unit
Scale to be used with this type.Default: NoneScale
Logical Node Name Plate (LPL)3.4.8.15.
Table 3.4.8.15-1 Configurable LPL properties for OPC client
DescriptionValue or Value range/ DefaultProperty/ Para-
meter
Basic
61850 Data ObjectLPL61850 Data Object
Data Class Spe-
cific
Text string describing serial number.User defined.
Default: ABB123456789
Serial number
Text string describing software revision.Default: 1.0Software Revision
Text string describing vendor.ABBVendor
Measured value (MV)3.4.8.16.
Table 3.4.8.16-1 Configurable MV properties for OPC client
DescriptionValue or Value range/ DefaultProperty/ Para-
meter
Basic
Common data class according to IEC
61850.
MVCommon Data
Class
Addresses
Indication index.-1 to 65535
Default: -1
Index
Sub-Type
40
1MRS756566
COM600 Station Automation Series
DNP 3.0
LAN/WAN Master
(OPC) 3.2
User's Guide