DescriptionValue or Value range/ DefaultProperty/ Para-
meter
Data Class Spe-
cific
Variation for control0 to 65535
Default: 2
Control Variation
Binary counter reading (BCR)3.4.8.5.
Table 3.4.8.5-1 Configurable BCR properties for OPC client
DescriptionValue or Value range/ DefaultProperty/ Para-
meter
Basic
Common data class according to IEC
61850.
BCRCommon Data
Class
Addresses
Indication index.-1 to 65535
Default: -1
Indication Index
Data Class Spe-
cific
Object number for counter.Binary counter (20)
Frozen counter (21)
Default: Binary counter (20)
Counter Object
Specifies the multiplier for current SI unit.Default: DekaMultiplier
SI unit for measurement as described in
IEC61850
Default: DimensionlessUnit
Binary controlled step position information (BSC)3.4.8.6.
Table 3.4.8.6-1 Configurable BSC properties for OPC client
DescriptionValue or Value range/
Default
Property/ Parameter
Basic
Common data class according to IEC 61850.BSCCommon Data Class
Addresses
Control index.-1 to 65535
Default: -1
Control Index
32
1MRS756566
COM600 Station Automation Series
DNP 3.0
LAN/WAN Master
(OPC) 3.2
User's Guide