EasyManuals Logo
Home>ABB>Controller>COM600 Station Automation Series

ABB COM600 Station Automation Series User Manual

ABB COM600 Station Automation Series
70 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #42 background imageLoading...
Page #42 background image
Controllable single point (SPC)3.4.8.17.
Table 3.4.8.17-1 Configurable SPC properties for OPC client
DescriptionValue or Value range/ DefaultProperty/ Para-
meter
Basic
Common data class according to IEC
61850.
SPCCommon Data
Class
Addresses
Control index.-1 to 65535
Default: -1
Control Index
Indication index.-1 to 65535
Default: -1
Indication Index
Data Class Spe-
cific
Momentary
Pulse
Latch
Default: Momentary
Control Code Quali-
fier
Object number for control.Default: Binary control output
block (12).
Control Object
Variation for control.0 to 65535
Default: 1
Control Variation
Object number for indication.Binary input (1, 2)
Binary output (10)
Default: Binary input (1, 2)
Indication Object
Specifies using two-step, select-before-
operate method for issuing control request
or not.
Direct Operate
Select Before Operate
Default: Direct Operate
Operate
Single point status (SPS)3.4.8.18.
Table 3.4.8.18-1 Configurable SPS properties for OPC client
DescriptionValue or Value range/ DefaultProperty/ Para-
meter
Basic
42
1MRS756566
COM600 Station Automation Series
DNP 3.0
LAN/WAN Master
(OPC) 3.2
User's Guide

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB COM600 Station Automation Series and is the answer not in the manual?

ABB COM600 Station Automation Series Specifications

General IconGeneral