ABB i-bus
®
KNX
Device technology
FCA/S 1.x.x.1 | 2CDC508134D0202 13
Maximum
communication objects
Fan Coil Actuator PWM/...*
* … = Current version number of the application. Please refer to the software information on our website for this purpose.
ETS and the current version of the device application are required for programming.
The current version of the application is available on the Internet for download at www.abb.com/knx.
After import into ETS it appears in the Catalogs window under Manufacturers/ABB/Heating, Ventilation,
Air Conditioning/Fan Coil Actuator PWM.
The device does not support the locking function of a KNX device in ETS. If you use a BCU code to
inhibit access to all the project devices, this has no effect on this device. Data can still be read and
programmed.
2.1.2 Valve outputs (thermoelectric, PWM)
4, non-isolated, short-circuit proofed
I
n
rated current (per output pair)
0.5 A resistive load at T
u
up to 20 °C
0.3 A resistive load at T
u
up to 60 °C
Maximum 1.6 A, 10 s at T
u
up to 60 °C
2.1.3 Valve outputs (motor-driven, 3-point)
2, non-isolated, short-circuit proofed
I
n
rated current (per output pair)
0.5 A resistive load at T
u
up to 20 °C
0.3 A resistive load at T
u
up to 60 °C
Maximum 1.6 A, 10 s at T
u
up to 60 °C
PT100 2-conductor technology,
PT1000 2-conductor technology,
A selection of KT/KTY 1,000/2,000,
Resolution, accuracy and tolerances
Between sensor and device input