2.3.7 Fan, lamp load 6 A
Lamps
Incandescent lamp load
1,200 W
Fluorescent lamps T5/T8
Uncompensated
Parallel compensated
DUO circuit
800 W
300 W
350 W
Low-voltage halogen lamps
Inductive transformer
Electronic transformer
800 W
1,000 W
Halogen lamps 230 V
1,000 W
Dulux lamp
Uncompensated
Parallel compensated
800 W
800 W
Mercury-vapor lamp
Uncompensated
Parallel compensated
1,000 W
800 W
Switching capacity (switching contact)
Maximum peak inrush current I
p
(150 s)
200 A
Maximum peak inrush current I
p
(250 s)
160 A
Maximum peak inrush current I
p
(600 s)
100 A
Number of electronic ballasts (T5/T8, single
element)
1)
18 W (ABB EVG 1 x 18 SF)
10
24 W (ABB EVG-T5 1 x 24 CY)
10
36 W (ABB EVG 1 x 36 CF)
7
58 W (ABB EVG 1 x 58 CF)
5
80 W (Helvar EL 1 x 80 SC)
3
1)
For multiple element lamps or other types, the number of electronic ballasts must be determined using the peak inrush current of the ballasts.