1SFC132005C0201, rev.F | Softstarters 25
PSS The flexible range
UL ratings
3-phase motor rating – In-Line
Softstarters Motor power P (hp) and full load current FLA (A)
U
e
U
e
U
e
U
e
Max. FLA 200V / 208V 220V / 240V 440V / 480V 550V / 600V
Type A hp hp hp hp
PSS18/30 18 5 5 10 15
PSS30/52 28 7.5 10 20 25
PSS37/64 34 10 10 25 30
PSS44/76 40 10 10 30 30
PSS50/85 47 15 15 30 40
PSS60/105 56 15 20 40 50
PSS72/124 67 20 20 50 60
PSS85/147 85 25 30 60 75
PSS105/181 105 30 40 75 100
PSS142/245 125 40 40 100 125
PSS175/300 156 50 60 125 150
PSS250/430 225 75 75 150 200
PSS300/515 248 75 100 200 250
3-phase motor rating – Inside Delta
Softstarters Motor power P (hp) and full load current FLA (A)
U
e
U
e
U
e
U
e
Max. FLA 200V / 208V 220V / 240V 440V / 480V 550V / 600V
Type A hp hp hp hp
PSS18/30 30 7.5 10 20 25
PSS30/52 48 15 15 30 40
PSS37/64 58 20 20 40 50
PSS44/76 69 20 25 50 60
PSS50/85 81 25 30 60 75
PSS60/105 96 30 30 75 75
PSS72/124 116 40 40 75 100
PSS85/147 147 50 50 100 150
PSS105/181 181 60 60 150 150
PSS142/245 215 75 75 150 200
PSS175/300 270 75 100 200 250
PSS250/430 389 125 150 300 400
PSS300/515 429 150 150 350 400