1SFC132005C0201, rev.F | Softstarters 49
PST(B) – The advanced range
UL ratings
3-phase motor rating – In-Line
Softstarters Motor power P (hp) and full load current FLA (A)
U
e
U
e
U
e
U
e
Max. FLA 200V / 208 V 220 V / 240 V 440 V / 480 V 550 V / 600 V
Type A hp hp hp hp
PST30 28 7.5 10 20 25
PST37 34 10 10 25 30
PST44 42 10 15 30 40
PST50 54 15 20 40 50
PST60 60 20 20 40 50
PST72 68 20 25 50 60
PST85 80 25 30 60 75
PST105 104 30 40 75 100
PST142 130 40 50 100 125
PST175 156 50 60 125 150
PST210 192 60 75 150 200
PST250 248 75 100 200 250
PST300 302 100 100 250 300
PSTB370 361 125 150 300 350
PSTB470 480 150 200 400 500
PSTB570 590 200 250 500 600
PSTB720 720 250 300 600 700
PSTB840 840 300 350 700 800
PSTB1050 1062 400 450 900 1000
3-phase motor rating – Inside Delta
Softstarters Motor power P (hp) and full load current FLA (A)
U
e
U
e
U
e
U
e
Max. FLA 200 V / 208 V 220 V / 240 V 440 V / 480 V 550 V / 600 V
Type A hp hp hp hp
PST30 42 10 15 30 40
PST37 54 15 20 40 50
PST44 72 20 25 50 60
PST50 80 25 30 60 75
PST60 104 30 40 75 100
PST72 104 30 40 75 100
PST85 130 40 50 100 125
PST105 156 50 60 125 150
PST142 192 60 75 150 200
PST175 248 75 100 200 250
PST210 302 100 100 250 300
PST250 361 125 150 300 350
PST300 480 150 200 400 500
PSTB370 590 200 250 500 600
PSTB470 720 250 300 600 700
PSTB570 840 300 350 700 800
PSTB720 1247 400 500 1000 1200
PSTB840 1454 500 600 1200 1500
PSTB1050 1839 600 700 1500 1800