5.3.3 Deactivation of Central Account Management from
PCM600
GUID-19BDC85E-4175-4B53-909F-0051E5D98492 v1
When Central Account Management is switched off in the IED, the IED will go
back to be open. There will not be any IED users defined even if that was the case
when Central Account Management was activated.
Instead the built-in, factory default users will be reactivated.
1. Right click on the Device in Account Management tool and select Edit as
shown in figure 52
IEC15000292 V1 EN-US
Figure 53: Deactivation of Central Account Management
2. Select Device CAM Mode as Disable as shown in fig
53
3. Click on Save & Close
button, to save and close manual configuration screen.
4. Right click on the Device, and select Write to IED as shown in fig
54
IEC15000293 V1 EN-US
Figure 54: Write configuration to IED
5. PCM600 output window indicates the result of the write operation as shown in
fig
55
1MRK 511 399-UEN B Section 5
Central Account Management
670 series 2.2 IEC 61
Cyber security deployment guideline