Four overcurrent stages are offered for overcurrent and short-circuit protection. Three
of them include directional functionality DPHxPDOC.
PHIPTOC1
BLOCK
ENA_MULT
OPERATE
START
PHIPTOC1_OPERATE
PHIPTOC1_START
GUID-9E341F53-8AB2-4A2C-B776-B26D19CAB8F9 V1 EN
Figure 279: Overcurrent protection function
DPHHPDOC1
BLOCK
ENA_MULT
NON_DIR
OPERATE
START
DPHLPDOC1
BLOCK
ENA_MULT
NON_DIR
OPERATE
START
DPHLPDOC2
BLOCK
ENA_MULT
NON_DIR
OPERATE
START
OR6
B1
B2
B3
B4
B5
B6
O
DPHLPDOC2_OPERATE
DPHLPDOC2_OPERATE
DPHHPDOC1_OPERATE
DPHHPDOC1_OPERATE
DPHLPDOC1_OPERATE
DPHLPDOC1_OPERATE
DPHLPDOC1_START
DPHLPDOC2_START
DPHHPDOC1_START
DPHxPDOC_OPERATE
GUID-C39AC382-EF6F-42D4-9F57-A295796FE592 V1 EN
Figure 280: Directional overcurrent protection function
The upstream blocking from the start of the second low stage of three-phase
directional overcurrent protection DPHLPDOC2 is connected to the binary output
X110:SO1. This output can be used for sending a blocking signal to the relevant
overcurrent protection stage of the IED at the infeeding bay.
OR6
B1
B2
B3
B4
B5
B6
O
UPSTEAM_OC_BLOCKINGDPHLPDOC2_START
GUID-AAA165D7-458D-41C8-9691-E402B65ADC68 V1 EN
Figure 281: Upstream blocking logic
1MRS756378 S Section 3
REF615 standard configurations
REF615 203
Application Manual