Channel ID text Level trigger mode
22 INTRPTEF1 - operate Level trigger off
23 EFHPTOC1 - operate Level trigger off
24 PDNSPTOC1 - operate Level trigger off
25 INRPHAR1 - blk2h Level trigger off
26 T1PTTR1 - operate Level trigger off
27 ROVPTOV1 - operate Level trigger off
ROVPTOV2 - operate
ROVPTOV3 - operate
28 ARCSARC1 - ARC flt det Level trigger off
ARCSARC2 - ARC flt det
ARCSARC3 - ARC flt det
29 ARCSARC1 - operate Positive or Rising
30 ARCSARC2 - operate Positive or Rising
31 ARCSARC3 - operate Positive or Rising
32 DARREC1 - inpro Level trigger off
33 DARREC1 - close CB Level trigger off
34 DARREC1 - unsuc recl Level trigger off
35 X120BI1 - ext OC blocking Level trigger off
36 X120BI2 - CB closed Level trigger off
37 X120BI3 - CB opened Level trigger off
3.3.3 Functional diagrams
The functional diagrams describe the default input, output, alarm LED and function-
to-function connections. The default connections can be viewed and changed with
PCM600 according to the application requirements.
The analog channels have fixed connections to the different function blocks inside the
IED’s standard configuration. However, the 12 analog channels available for the
disturbance recorder function are freely selectable as a part of the disturbance
recorder’s parameter settings.
The phase currents to the IED are fed from a current transformer. The residual current
to the IED is fed from either residually connected CTs, an external core balance CT,
neutral CT or internally calculated.
The residual voltage to the IED is fed from either the residually connected VTs or an
open delta connected VT.
The IED offers six different settings groups which can be set based on individual
needs. Each group can be activated or deactivated using the setting group settings
available in the IED.
1MRS756378 S Section 3
REF615 standard configurations
REF615 53
Application Manual