Channel ID text Level trigger mode
34 DARREC1 - unsuc recl Level trigger off
34 X120BI1 - ext OC blocking Level trigger off
35 X120BI2 - CB closed Level trigger off
36 X120BI3 - CB opened Level trigger off
3.4.3 Functional diagrams
The functional diagrams describe the default input, output, alarm LED and function-
to-function connections. The default connections can be viewed and changed with
PCM600 according to the application requirements.
The analog channels have fixed connections to the different function blocks inside the
IED’s standard configuration. However, the 12 analog channels available for the
disturbance recorder function are freely selectable as a part of the disturbance
recorder’s parameter settings.
The phase currents to the IED are fed from a current transformer. The residual current
to the IED is fed from either residually connected CTs, an external core balance CT,
neutral CT or internally calculated.
The residual voltage to the IED is fed from either the residually connected VTs or an
open delta connected VT.
The IED offers six different settings groups which can be set based on individual
needs. Each group can be activated or deactivated using the setting group settings
available in the IED.
Depending on the communication protocol the required function block needs to be
instantiated in the configuration.
3.4.3.1 Functional diagrams for protection
The functional diagrams describe the IEDs protection functionality in detail and
according to the factory set default connections.
Four overcurrent stages are offered for overcurrent and short-circuit protection.
Three-phase non-directional overcurrent protection, instantaneous stage, PHIPTOC1
can be blocked by energizing the binary input X120:BI1.
Section 3 1MRS756378 S
REF615 standard configurations