7.5.5 Selecting IED blocked or IED test and blocked mode
The IED blocked mode and the IED test and blocked mode can be activated using
the LHMI. The Home button flashes green when the device is in the IED blocked or
IED test and blocked mode. By default, the test mode can only be changed from the
LHMI. Activation by remote client is possible, see the technical manual.
The test mode can be used for simulated testing of functions and outputs without
providing current inputs. The IED blocked mode can be used to block the physical
outputs to the process.
Select Testing and Commissioning> Test mode> IED blocked or IED test and
blocked to activate the IED blocked mode and the IED test and blocked mode.
Table 28: Test mode
Test mode Description Protection
BEH_BLK
Protection
BEH_TST
Normal mode Normal operation FALSE FALSE
IED blocked Protection works as in “Normal
mode” but the ACT configuration
can be used to block physical out-
puts to process. Control function
commands are blocked.
TRUE FALSE
IED test Protection works as in “Normal
mode” but protection functions
work in parallel with test parame-
ters
FALSE TRUE
IED test and
blocked
Protection works as in “Normal
mode” but protection functions
work in parallel with the test pa-
rameter. The ACT configuration
can be used to block physical out-
puts to process. The control func-
tion command is blocked.
TRUE TRUE
If the IED blocked or IED test and blocked mode is not cancelled, it
remains on and the Home button remain flashing.
7.6 ABB Product Data Registration
The ABB Product Data Registration feature traces composition changes in the
protection relay's SW or HW. Traceability allows better support and maintenance
possibilities.
Protection relay detects hardware or software change and stores this information
internally. This information can be read from relay using PCM600 Lifecycle
Handling> Collect IED Composition Data.
Composition data is automatically transferred to ABB if feature is enabled during
the PCM600 installation.
1MRS759118 D
Commissioning
REX640
Operation Manual
151

Table of Contents

Other manuals for ABB RELION REX640

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB RELION REX640 and is the answer not in the manual?

ABB RELION REX640 Specifications

General IconGeneral
BrandABB
ModelRELION REX640
CategoryProtection Device
LanguageEnglish

Related product manuals