case. The AIM1 analog input card provides the best match for
them with five voltage and five current inputs, one being a
sensitive input.
3I (HV)
CONDITION MONITORING
AND SUPERVISION
10100011001100
101100101110010
1100111011010
10110110110100
1010001100110010100011001100
101100101110010
1100111011010
10110110110100
PROTECTION AND CONTROL RELAY
Example of a combination of application packages for transformer protection
PROTECTION
LOCAL HMI (OPTIONAL)
REX640
REMARKS
Total nr. of instances
APPLICATION PACKAGE FOR POWER TRANSFORMER PROTECTION
3 WINDING ADD-ON PACKAGE FOR TRANSFORMER PROTECTION
APPLICATION PACKAGE FOR OLTC CONTROL
APP8
APP10
ALSO AVAILABLE
- Disturbance and fault recorders
- Sequence event recorder
- Relay self-supervision
- User management and logging
- Logical and mathematical functions
- WebHMI
COMMUNICATION
Protocols:
IEC 61850-8-1/-9-2LE
Modbus
®
IEC 60870-5-103
DNP3
Interfaces:
Ethernet: TX (RJ45), FX (LC)
Serial: Serial glass fiber (ST),
RS-485
Redundant protocols:
HSR
PRP
Time synchronization:
SNTP
PTPv2
IRIG-B
- 7-inch color touch screen
- Ready-made pages and
customizable pages
- Increased situational awareness
towards process
- Supports Relay testing and
commissioning
- Graphical editing of pages with
PCM600 tool
Master Trip
94/86
Master Trip
94/86
Master Trip
94/86
MEASUREMENT
- I, U, Io, Uo, P, Q, E, pf, f
- Sequence current/voltage measurement
- Limit value supervision
- RTD/mA measurement and mA output
3Ith>T/G/C
49T/G/C
MCS 3I,I2
CCM 3I,I2
OLGAPC
OLGAPC
3dI>3W
87T3
3dI>T
87T
COLTC
90V
TPOSM
84T
3U
LOADPROF
LOADPROF
PQM3IH
PQM ITHD, IDC
PQM3VH
PQM VTHD, VDC
PQUUB
PQMV UB
3Ihp>T
26/49HS
Ctrl
1)
Ind
2)
CONTROL AND INDICATION
Object
CB -
DC, 3 state
DC
8
6
ES 3
Control and status indication function for
primary object
Status indication function for primary
object
1)
2)
3
8
6
3
U/f>
24
CBCM
52CM
FUSEF
VCM, 60
MCS 3I
CCM
7×
Io
3I
3I
APP8
ADD2
APP10
RTD
mA/Ω
3U
Uo
Analog interface types
2x AIM2
+ RTD1
Current transformer 12
Voltage transformer 8
RTD measurement 10
mA input/output 2
CVPSOF
SOFT
Io>>→
67G/N-2
51G/N-2
3I>→
67P/
51P-1
Uo>
59G/59N
4×
U2>
59NS
4×
U1>
59PS
4×
U1<
27PS
4×
4×
3I>>>
50P
Io>→
67G/N-1
51G/N-1
4×
I2>M
46M
GUID-CBE90DC2-08A4-425C-A34B-02FBA3D95004 V2 EN
Figure 8. Transformer application
F
igure 8 presents REX640 in a three-winding power transformer
application. The base functionality is enhanced with a power
transformer application package and the related three-winding
add-on package. In the example case, REX640 also manages
the on-load tap changer’s manual and automatic control. For
this purpose, the application package for OLTC control has
1MRS759144 A
Product version: 1
ABB 11