8 1VLG5 00007 E
KEVA 24 B20
KEVA B sensor can be used in all applications up to the voltage level 24 kV. The sensor fulfils
requirements of accuracy class 0.5 for measurement purposes and accuracy class 3P for
protection purposes.
Figure 6: Voltage sensor KEVA 24 B20
Technical parameters
– Rated primary voltage 22 / 3 kV
– Rated power frequency withstand voltage 50 kV
– Rated lightning impulse withstand voltage 125 kV
– Transformation ratio 10 000: 1
– Accuracy class 0.5 / 3P