48 1VLG5 00007 E
In the IED Capabilities tab, check the
Override for Client Service SampledValues
box to adjust
the IED615 / IED620 option to support sampled values services.
Figure 63: Editing 615 series capabilities
Step 3 / 5
Configuring sampled value control block in the IET600
Figure 64: Sampled value control block
Step 4 / 5
Connecting the SMV senders and receivers in the IET600
Figure 65: Connecting the SMV senders and receivers
Step 5 / 5
Save and export the SCD file and import it to PCM600