EasyManuals Logo
Home>ABB>Switch>UniGear Digital

ABB UniGear Digital User Manual

ABB UniGear Digital
112 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #78 background imageLoading...
Page #78 background image
66 1VLG5 00007 E
SINGLE network
+ RSTP
PRP networks
HSR network
Data loss
Yes
No
No
ECONOMICS
Equipment costs
Medium, Ethernet
switches
High, double amount of
Ethernet switches, pro-
tection relay with more
interfaces
Medium, Redbox, protec-
tion relay with more in-
terfaces
Communication Links
Medium, links between
protection relays and
Ethernet switches
High, double links be-
tween protection relays
and Ethernet switches
Low, only links between
protection relays
Space requirements
Medium, Ethernet
switches
High, Ethernet switches
Low, less devices
ENGINEERING
Effort
Less
More
Less
3.5.4 Ethernet traffic estimation
MMS 0.01 Mbps per a single protection relay
GOOSE 0.1 Mbps in burst conditions per a single protection relay (2 data sets)
SMV 5 Mbps per a source protection relay
Fast Ethernet = 100 Mbps
The bandwidth of the HSR ring is half of the Fast Ethernet, because each message is sent in
parallel into either direction.
For instance, estimated Ethernet traffic volume for a substation consisting of two sections
(20x GOOSE sender, 2x SMV sender) is: 20 x 0.01 + 20 x 0.1 + 2 x 5 = 12.2 Mbps
Knowledge of data flows and traffic patterns allows for detecting bottlenecks and planning
the network segmentation and segregation of traffic.

Table of Contents

Other manuals for ABB UniGear Digital

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB UniGear Digital and is the answer not in the manual?

ABB UniGear Digital Specifications

General IconGeneral
BrandABB
ModelUniGear Digital
CategorySwitch
LanguageEnglish

Related product manuals