ENGINEERING ETHE RNE T
1VLG5 00007 E 59
Other recommended type of substation clock is LANTIME M400 manufactured by Meinberg.
It supports GPS / GLONASS clock and synchronization of IEEE 1588-2008 (PTPv2) compatible
clients via IEEE C37.238-2011 Power Profile, two step clock. Refer to www.meinberg.de for
additional information.
Figure 79: Example of satellite controlled clock from Meinberg
Layout
The communication devices are usually mounted inside the low voltage compartment of the
panel. Therefore, the panels are ready for connection. The main benefits of this solution are:
Cubicles are ready for connection
Saving space in substation building
Shorter communication links
Cheaper solution
Protection relays are connected to the Ethernet network in compliance with the Network
Overview Diagrams. It is recommended to wire communication link from Ethernet switch to
protection relays and keep minimal allowed bend radius especially for fiber optic patch cords.
Figure 80: Low Voltage Compartment of UniGear panel

Table of Contents

Other manuals for ABB UniGear Digital

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB UniGear Digital and is the answer not in the manual?

ABB UniGear Digital Specifications

General IconGeneral
BrandABB
ModelUniGear Digital
CategorySwitch
LanguageEnglish

Related product manuals