4.5 QUIET MODE
00 00
01 01
02 02
23 59
22 58
Quiet mode
Quiet mode: Timer
Start Timer: 00:00
End Timer: 00:00
At the function setting page with the unit turned o, by touching “Quiet mode”,
there will be a choice box, where “Quiet mode” can be set to “O”, “One time”, “Tim-
er” or “Always ON”.
When it is set to "One time", it will automatically back to "O" when the main unit
is turned o.
When it is set to "Always ON", this function can be deactivated only through chang-
ing its setting, and would not be deactivated as the main unit is turned o.
When it is set to “Timer”, it is also required to set the “Start timer” and “End timer”.
Unless otherwise stated, otherwise time setting is all the same.
To set the values, press the time label in question and set the hours and minutes by
sliding the value up or down with your ngertip (the value highlighted in blue in
the middle of the selection window), as shown in the gure:
00 00
01 01
02 02
23 59
22 58
Quiet mode
Quiet mode: Timer
Start Timer: 00:00
End Timer: 00:00
This setting will be saved by touching the corner at the upper right corner.
Note:
— The function can still be set if the unit is O, but it will only be implemented if
the unit is activated;
— When the function is set to “On”, it will automatically be set to “O” if the unit is
switched o manually, whereas the setting will remain valid until the end of the
selected period if the function value is set to “Clock timer”;
— If the relative function is activated (paragraph "8.1Activating/deactivating the
memory (On/o memory)p.32"), the value of this parameter will be stored in
the memory and automatically reset after any possible voltage failure.
4.6 ENERGYSAVING MODE
Weather depend (1/3)
Weather depend: O
Upper AT Heat: 25°C
Lower AT Heat: -20°C
Upper WT Heat: 55°C
Lower WT Heat: 40°C
After accessing the “Weather depend” function, you can set all the parameters re-
lated to osetting work set-points in accordance with variations in outside air tem-
perature.
To activate this function, click on the “Weather depend“ label (the rst item on the
rst page of the function). Select “On” and then conrm with “OK”.
Weather depend
On
O
OK Cancel
Subsequently, the values for the various parameters that make up climatic curves
will be set; these parameters represent the curves that the system will use to
change the set automatically on the delivery temperature or the ambient air tem-
perature (if an air-based control has been set, using the specic accessory air probe)
to both hot and cold:
Lower AT
Upper AT
Upper WT
Upper RT
Lower WT
Lower RT
To set values for each parameter to create the climatic curves, click on the label of
the parameter in question and set the desired value using the "+" or "-" keys to en-
ter a value within the permitted range. After setting the value, press “OK” to conrm
and return to the higher level;
+-
25°C
Upper AT Heat
Range: 10~37°C Default: 25°C
OK Cancel
Note:
— The function remains active even when the unit has been switched o. To deac-
tivate it, set “Weather depend: O manually.”;
— In the “View” menu, you can see the target value of the climatic curve;
— When this function has been activated, it is still allowed to set the room tem-
perature, however, this setting becomes valid only when “Weather depend” has
been deactivated.
— The function can still be set if the unit is OFF, but it will only be implemented if
the unit is activated;
— The climatic curves can only be applied to heating and cooling, not to domestic
hot water production;
— If the relative function is activated (paragraph "8.1Activating/deactivating the
memory (On/o memory)p.32"), the value of this parameter will be stored in
the memory and automatically reset after any possible voltage failure;
— When the set point of the maximum temperatures is lower than that of the min-
imum temperatures, a message will advise to reset the temperatures.