6 COMMISSION MENU
At the menu page, by touching “Commission” and then entering the correct pass-
word (000048) in the pop-up window, the commissioning parameter page will be
accessed, where the left side is for the function setting and the right side is for the
parameter setting, as shown in the gure below:
Commission
Function Param.
PASSWORD: 000048
This menu is used to make the settings needed for correct unit operation: the logics,
the components installed on the system and the accessories envisaged for each
installation will be set using the functions in this menu.
The information in the menu is sub-divided into two large macro groups:
— “Function“ (containing the settings and any functions needed for unit opera-
tion);
— “Parameter“ (containing the general operating parameters);
1 2
3 4
Function (1/4)
Ctrl. state: T water out
Cool 2 way valve: On
Heat 2 way valve: O
Solar setting: Without
Water tank: With
1 2
3 4
Parameter (1/1)
T HP max: 50°C
Cool run time: 5 min
Heat run time: 3 min
To navigate the “Function” or “Parameter“ sub-menu, use the following keys:
1. Move back to the previous page;
2. Move on to the next page;
3. Go back to the higher level menu;
4. Go back to the main page;
NOTE: if the relative function is activated (paragraph "8.1Activating/deactivating
the memory (On/o memory)p.32"), the value of these parameters will be stored
in the memory and automatically reset after any possible voltage failure.
WARNING: these functions and parameters must only be set and/or mod-
ied by authorised personnel with the necessary technical skills to install
and maintain these units. Incorrect settings may lead to malfunctioning or
damage to the unit and the system!
Commissioning Function Setting
Number Displayed name Range Default Note
1 Ctrl.state T-water out / T-room T-water out When “Remote sensor” is set to “With”, it can be set to “T-room”.
2 2-Way valve
Cool 2-Way valve O
It will decide the status of the 2-way valve under the “Cool” and
“Cool + Hot water” modes.
Under “Cool” or “Cool + Hot water” mode, the status of the
2-way valve depends on this setting. This setting is unavailable
to heating only units.
Heat 2-Way valve On
It will decide the status of the 2-way valve under the “Heat” and
“Heat + Hot water” modes.
5 Solar setting With / Without Without
When the water tank is unavailable, this setting will be
reserved.
When it is set to “With”, the solar kitting will work on its own.
When it is set to “Without”, hot water by the solar kitting is
unavailable.
6 Water tank With / Without Without --
7 Thermostat
Without / Air / Air+ hot water / Air+ hot
water2
Without
This setting cannot be interchanged among “Air” , “Air+ hot
water” and “Air+ hot water2” directly but via “Without” this
option.
8 Other thermal With / Without Without --
9 Electric heater O / 1 / 2 O --
10 Ambient sensor With / Without Without
When it set to “Without”, and the “Ctrl. state” will be defaulted
to be “T-water out”.
11 Air removal On/O O --
12 Floor debug On/O O --
13 Manual defrosting On/O O --
14 Force mode O / Force-cool / Force-heat O --
15 Tank heater Logic 1 / Logic 2 Logic 1
This setting is allowed when the water tank is available and the
unit is OFF.
16 External contact On/O O --