6.11 SETTING THE PREHEATING PROCEDURE FOR RADIANT PANELS FLOOR DEBUG
At the commissioning parameter setting page, by touching “Floor debug”, the con-
trol panel will access to the corresponding setting page.
Start
Floor debug: On
Segments: 2
Period 1 temp: 25°C
Segment time: 12H
∆T of segment: 5°C
After accessing the “Floor debug” function, you can activate or deactivate any pos-
sible procedure for pre-heating the radiant panels. This procedure creates a heating
cycle during which the temperature is kept stable for a certain time (period), then
increased by a value equal to T indicated, and kept there for the next period. This
temperature increase and hold procedure will be repeated for the number of peri-
ods specied.
Floor debug
Number Name Displayed name Range Default
Accuracy
1 Floor debug switch Floor debug On/O O /
2 Quantity of segments Segments 1~10 1 1
3 Temperature of the rst segment Period 1 temp 25~35°C 25°C 1°C
4 Duration of each segment Segment time 12~72 hours 0 12 hours
5 Temperature dierence of each segment T of segment 2~10°C 5°C 1°C
At the end, press the button at the top right to start (or interrupt) the pre-heating
cycle.
Note:
This function can be activated only when the unit is turned o. When it is done
with the unit keeping "On", a warning will appear telling you to turn o the
unit rst;
When this function has been activated, “On/O operation will be deactivated.
By pressing On/O, a warning will appear telling you to turn o the function;
During the execution of this function, all other functions are disabled;
Upon power failure, function will back to “O and the runtime will be zeroed;
When “Floor debug” has been activated, T-oor debug and “Debug time” can
be viewed;
When “Floor debug” has been activated and works normally; the corresponding
icon will be displayed at the upper side of the menu page;
Before activating “Floor debug”, make sure “Segment time” of each segment is
not zero. If so, a warning will appear telling you that the time is wrong. In this
case, “Floor debug” is allowed to be activated only when “Segment time” has
changed.