EasyManuals Logo
Home>AERMEC>Controller>HMI-1

AERMEC HMI-1 User Manual

AERMEC HMI-1
36 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #19 background imageLoading...
Page #19 background image
19
Number Displayed name Range Default Note
17 Current limit O / Current limit / Power limit O
Current limit: it ranges from 0 to 100A and the default is 16A.
Power limit: it ranges from 0.0 to10.0kW and the default is 3,0
kW.
Minimal value: 0~15A, 1A defaulted.
Electric heater: the user is allowed to set the power from
0~15kW, 3kW defaulted.
18 Address 1~125] [127~253] 1 --
19 Refri. recovery On/O O --
20 Memory contact On/O O --
21 3-Way valve1 Without / DHW / AIR Without --
22 Hot water control mode Auto / Manual Auto
23 SG On/O O
24 Cool control mode On/O O
25 Heat control mode On/O O
26 HWPS Limit Function On/O O
There are three highest speeds of the water pump: high,
medium, low.
27 Water pump antistall On/O O
Water pump antistall interval: 1~12h, 2h defaulted;
Water pump antistall duration: 10~100s, 30s defaulted;
Commissioning Parameters Setting
Number Name Displayed name Range Default Note
1 T-HP max T-HP max 40~55°C 50°C
6.1 SETTING THE CONTROL LOGIC CTRL.STATE
At the commissioning parameter setting page, by touching “Ctrl. state, it can be set
to “T-water out” or “T-room.
Ctrl. state
T room
T water out
OK Cancel
After accessing the “Ctrl.state function, you can choose whether to base the unit
control logic on the processed water temperature or on the ambient air temper-
ature (if the air probe accessory is installed and correctly set). Select the required
logic, then press “OK” to conrm.
Note:
If the ambient air probe accessory is not installed (and correctly set), you can
only choose “T-water out”;
If the relative function is activated (paragraph "8.1 Activating/deactivating
the memory (On/o memory)p.32"), the value of these parameters will be
stored in the memory and automatically reset after any possible voltage failure.
6.2 SETTING THE STATUS OF THE 2WAY VALVE IN
COOLING MODE COOL 2WAY VALVE
Cool 2 way valve
On
O
OK Cancel
After accessing the “Cool 2-Way valve function, you can set the status of the 2-way
valve in cooling mode (for more information about the assembly and use of the
2-way valve, refer to the installation manual). Select the required logic, then press
“OK” to conrm.
It is optional. When there is a radiant oor system and radiators, it can be used to
control the system.
Note:
If you select the “O status, the valve will be CLOSED in cooling mode; it will be
OPEN if you select “On”;
If the relative function is activated (paragraph "8.1 Activating/deactivating
the memory (On/o memory)p.32"), the value of these parameters will be
stored in the memory and automatically reset after any possible voltage failure.
6.3 SETTING THE STATUS OF THE 2WAY VALVE IN
HEATING MODE HEAT 2WAY VALVE
On
O
OK Cancel
Heat 2 way valve
After accessing the “Heat 2-Way valve function, you can set the status of the 2-way
valve in heating mode (for more information about the assembly and use of the
2-way valve, refer to the installation manual). Select the required logic, then press
“OK” to conrm.
Note:
1. If you select the “O status, the valve will be CLOSED in heating mode; it will
be OPEN if you select “On”;
2. If the relative function is activated (paragraph "8.1 Activating/deactivating
the memory (On/o memory) p. 32"), the value of these parameters will
be stored in the memory and automatically reset after any possible voltage
failure.
6.4 SETTING SOLAR SYSTEM INTEGRATION SOLAR
SETTING
Function currently NOT AVAILABLE.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the AERMEC HMI-1 and is the answer not in the manual?

AERMEC HMI-1 Specifications

General IconGeneral
BrandAERMEC
ModelHMI-1
CategoryController
LanguageEnglish

Related product manuals