146 Rockwell Automation Publication 1734-UM013C-EN-P - August 2010
Appendix E I/O Assemblies
Output Assemblies
364 1734-IB8S Safety and
Standard
0 Safety
Input 7
Safety
Input 6
Safety
Input 5
Safety
Input 4
Safety
Input 3
Safety
Input 2
Safety
Input 1
Safety
Input 0
1 Safety
Input 7
Status
Safety
Input 6
Status
Safety
Input 5
Status
Safety
Input 4
Status
Safety
Input 3
Status
Safety
Input 2
Status
Safety
Input 1
Status
Safety
Input 0
Status
2 Reserved Test
Output 3
Status
Test
Output 2
Status
Test
Output 1
Status
Test
Output 0
Status
3 Reserved Input
Power
Error
(1)
Reserved Muting
Lamp 3
Status
Muting
Lamp 1
Status
383 1734-IB8S Standard 0 Reserved Input
Power
Error
1 Reserved Test
Output 3
Status
Test
Output 2
Status
Test
Output 1
Status
Test
Output 0
Status
244 1734-OB8S Safety and
Standard
0 Safety
Output 7
Status
Safety
Output 6
Status
Safety
Output 5
Status
Safety
Output 4
Status
Safety
Output 3
Status
Safety
Output 2
Status
Safety
Output 1
Status
Safety
Output 0
Status
404 1734-OB8S Safety and
Standard
0 Safety
Output 7
Status
Safety
Output 6
Status
Safety
Output 5
Status
Safety
Output 4
Status
Safety
Output 3
Status
Safety
Output 2
Status
Safety
Output 1
Status
Safety
Output 0
Status
1 Safety
Output
Monitor 7
Safety
Output
Monitor 6
Safety
Output
Monitor 5
Safety
Output
Monitor 4
Safety
Output
Monitor 3
Safety
Output
Monitor 2
Safety
Output
Monitor 1
Safety
Output
Monitor 0
414 1734-OB8S Safety and
Standard
0 Safety
Output
Monitor 7
Safety
Output
Monitor 6
Safety
Output
Monitor 5
Safety
Output
Monitor 4
Safety
Output
Monitor 3
Safety
Output
Monitor 2
Safety
Output
Monitor 1
Safety
Output
Monitor 0
1 Reserved Combined
Output
Status
Reserved Output
Power
Error
Reserved
(1) This data is diagnostic only and does not have safety integrity.
Instance
Hex (decimal)
Module Connection
Type
Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
Instance
Hex (decimal)
Module Connection
Typ e
Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
21 1734-IB8S Safety
(1)
0 Reserved Standard
Output 3
Standard
Output 2
Standard
Output 1
Standard
Output 0
234 1734-OB8S Safety Only 0 Safety
Output 7
Safety
Output 6
Safety
Output 5
Safety
Output 4
Safety
Output 3
Safety
Output 2
Safety
Output 1
Safety
Output 0
(1) Only outputs 1 and 3 are configurable to Muting or Test Outputs. This assembly is accessible only over a Safety connection.