Rockwell Automation Publication 1756-UM013B-EN-P - October 2019 73
1756-OBV8S Output Module Features Chapter 4
Forcing
Use a force to override data that your logic either uses or produces.
Test and debug your logic.
Temporarily maintain normal system operations when an input device
has failed.
Use forces only as a temporary measure. They are not intended to be a permanent
part of your application.
Make sure that you understand this before you use forces.
Enable Forces
For a force to take effect, you enable forces. You can only enable and disable forces
at the controller level.
You can enable I/O forces and SFC forces separately or simultaneously.
You cannot enable or disable forces for a specific module, tag collection, or
tag element.
IMPORTANT When a safety signature exists, forcing safety I/O is not permitted in the safety
portion of the application.
ATTENTION: Forcing can cause unexpected machine motion that could
injure personnel. Before you use a force, determine how the force affects
your machine or process and keep personnel away from the machine area.
Enabling I/O or SFC forces causes your machine or process to go to another
state or phase.
Removing forces can still leave forces in the enabled state.
If forces are enabled and you install a force, the new force immediately
takes effect.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Allen-Bradley 1756-OBV8S and is the answer not in the manual?

Allen-Bradley 1756-OBV8S Specifications

General IconGeneral
BrandAllen-Bradley
Model1756-OBV8S
CategoryControl Unit
LanguageEnglish

Related product manuals