116 Rockwell Automation Publication 5069-UM004A-EN-P - April 2019
Chapter 4 Output Module Features
Short Circuit Protection with Safety Output Modules
Table 30 describes what happens when a short circuit condition is detected on
a Compact 5000 I/O safety output module.
Table 31 describes what happens when the short circuit condition is removed
from a Compact 5000 I/O safety output module and the data is set to safe
state, that is, the off state.
For more information on the maximum current that you can apply to an
output, see the Compact 5000 I/O Modules and EtherNet/IP Adapters
Technical Data, publication
5069-TD001.
Table 30 - Short Circuit Protection - Compact 5000 I/O Safety Output Modules
Output Behavior Tag Value Diagnostic Value I/O Status Indicator
State
• Faults
• Turns off
One of the following:
• If the output point is
shorted to 24V DC, the
I.Ptxx.ShortCircuit
tag = 1.
• If the output point is
shorted to ground, no tags
are changed.
One of the following:
• If the output point was
shorted to 24V DC when
the short circuit condition
was detected, the Short
Circuit diagnostic = 1.
• If the output point is
shorted to ground when
the short circuit condition
was detected, the Short
Circuit to Ground
diagnostic = 1.
One of the following:
• Flashes red if the
output point is
shorted to 24V DC.
• Off if the output
point is shorted to
ground.
Table 31 - Short Circuit Protection - Compact 5000 I/O Safety Output Modules
Output Behavior Tag Value Diagnostic Value I/O Status Indicator
State
Restarts in its
commanded state
One of the following:
• If the output point is
shorted to 24V DC, the
I.Ptxx.ShortCircuit
tag = 0.
• If the output point is
shorted to ground, no tags
are changed.
One of the following:
• If the output point was
shorted to 24V DC when
the short circuit condition
was detected, the Short
Circuit diagnostic = 0.
IMPORTANT: You must
cycle power to the module
to reset the diagnostic.
• If the output point is
shorted to ground when
the short circuit condition
was detected, the Short
Circuit to Ground
diagnostic = 0.
Turns off if there is no
longer a load that is
connected to the
output.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Allen-Bradley 5069-OBV8S and is the answer not in the manual?

Allen-Bradley 5069-OBV8S Specifications

General IconGeneral
BrandAllen-Bradley
Model5069-OBV8S
CategoryI/O Systems
LanguageEnglish

Related product manuals