Rockwell Automation Publication 5069-UM004A-EN-P - April 2019 125
Output Module Features Chapter 4
Fault State Duration After Connection Fault
If you configure the output to transition to a specific value after the connection
breaks, you must define how long the output remains at the specified value
before it transitions to a Final Fault State.
You can configure the output to remain at the specific value for the following
times:
•Forever
• 1 second
• 2 seconds
• 5 seconds
• 10 seconds
After the Fault State Duration time expires, the output transitions to user-
defined Final Fault State Value.
Final Fault State Value
The Final Fault State value defines the value to which the output goes after the
Fault State Duration time expires.
You set the value in the C.Ptxx.FaultFinalState tag. For more information on
module s, see Appendix B,
Module Tag Definitions on page 231.
Output State Once Connection Is Re-established
Once the connection between the owner-controller and output module is re-
established, the output resumes normal operation.
To see where to configure the Connection Fault Handling parameters, see the
following:
• 5069-OA16 module -
page 182
• 5069-OB8 module -
page 183
• 5069-OB16 and 5069-OB16K modules -
page 184
• 5069-OB16F module -
page 185
• 5069-OW4I module -
page 186
• 5069-OW16 module -
page 187
• 5069-OX4I module -
page 188

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Allen-Bradley 5069-OBV8S and is the answer not in the manual?

Allen-Bradley 5069-OBV8S Specifications

General IconGeneral
BrandAllen-Bradley
Model5069-OBV8S
CategoryI/O Systems
LanguageEnglish

Related product manuals