268 Rockwell Automation Publication 5069-UM004A-EN-P - April 2019
Appendix B Module Tag Definitions
5069-IB8S and 5069-IB8SK
Module Tags
This section describes the tags that are associated with the 5069-IB8S or
5069-IB8SK module.
Input Tags
Table 89 describes the 5069-IB8S or 5069-IB8SK module input tags.
5069-OBV8S
SIL2 CPU
5069-L3100ERMS2
Compact GuardLogix
5069-OBV8S
5069-IB8S5069-IB8S
OUTPUT OUTPUT
SA Power MOD Power
Safety Modules
Table 89 - 5069-IB8S or 5069-IB8SK Module Input Tags
Name Data Type Definition Valid Values
RunMode BOOL Module’s operating state • 0 = Idle
• 1 = Run
ConnectionFaulted BOOL Indicates if a connection is running.
The module sets this tag to 0 when connected. If the
module is not connected, it changes the tag to 1.
• 0 = Connection running
• 1 = Connection not running
DiagnosticActive BOOL Indicates if any diagnostics are active or if the prognostics
threshold is reached.
• 0 = No diagnostics active
• 1 = One or more diagnostics are active or the
prognostics threshold is reached
DiagnosticSequenceCount SINT Increments for each time a distinct diagnostic condition is
detected, and when a distinct diagnostic condition
transitions from detected to not detected.
Set to zero by product reset or power cycle. Wraps from
255 (-1) to 1 skipping zero.
• 1…255
The value of 0 is skipped except during module
power-up.
Ptxx.Data BOOL Indicates the current safety input value. • 0 = Off
• 1 = On
Ptxx.Fault BOOL Indicates one of the following:
• The channel data is inaccurate and cannot be trusted
for use in the application.
For more information, see
Module Data
Quality Reporting on page 71.
• The channel is set to Not Used.
• 0 = Good data
• 1 = Bad data (faulted) or set to Not Used
If the tag is set to 1, you must troubleshoot the
module to correct the cause of the inaccuracy.
IMPORTANT: Once the condition that causes
the tag to change to 1 is removed, you must
complete the steps described in
Safety Input
Fault Recovery on page 138 to reset this tag
to 0.
If the tag is 1 because the channel is set to Not
Used, no action is required.
Ptxx.Uncertain BOOL Indicates that the channel data can be inaccurate but the
degree of inaccuracy is not known.
For more information, see
Module Data Quality Reporting
on page 71.
• 0 = Good data
• 1 = Uncertain data
This tag is set to 1 when the module has
reached a critical operating temperature or is
higher the acceptable operating temperature.
IMPORTANT: Once the condition that causes
the tag to change to 1 is removed, the tag
automatically resets to 0.
Ptxx.ShortCircuit BOOL Indicates a short circuit. • 0 = No short circuit
• 1 = Short circuit
Ptxx.Status BOOL Indicates the status of the channel. • 0 = Bad, causing a fault
• 1 = Good
Testxx.Readback BOOL Indicates that a 24V DC power source is present at the
test output.
• 0 = 24V DC power is not present
• 1 = 24V DC power is present

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Allen-Bradley 5069-OBV8S and is the answer not in the manual?

Allen-Bradley 5069-OBV8S Specifications

General IconGeneral
BrandAllen-Bradley
Model5069-OBV8S
CategoryI/O Systems
LanguageEnglish

Related product manuals