Rockwell Automation Publication 5069-UM004A-EN-P - April 2019 49
Digital Module Operation in a Control System Chapter 1
Input Module Operation
Logix 5000 controllers do not poll the Compact 5000 I/O standard or safety
input modules for input data.
The data exchange process between the input modules and the controller
differs based on whether the module is a local I/O module or remote I/O
module.
Local Compact 5000 I/O Digital Input Modules
Local Compact 5000 I/O digital input modules broadcast their input data,
that is, channel and status data, to the system backplane at the time that is
defined in the RPI.
At the RPI, the following events occur.
1. The local input module scans its channels for input data.
2. The module sends the data to the system backplane.
3. The controller receives the data immediately.
Trigger Events for Standard Input Modules
Some Compact 5000 I/O standard input modules can trigger an event. For
example, the modules can trigger the Event task. The event task lets you
execute a section of logic immediately when an event, or receipt of new data,
occurs.
The following can trigger events:
• An input state change.
• A counting input done bit change.
• A pattern of input state changes on multiple module inputs.
For more information on how to use a Compact 5000 I/O standard input
module to trigger an event, see
Events on page 93.
5069-OBV8S
SIL2 CPU
5069-L3100ERMS2
Compact GuardLogix
5069-OBV8S
5069-IB8S5069-IB8S
OUTPUT OUTPUT
SA Power MOD Power
DC INPUT
5069-IB16
DC OUTPUT
5069-OB16
ANALOG INPUT
5069-IY4
SA Power MOD Power
ANALOG OUTPUT
5069-OF8
DC INPUT
5069-IB16
Standard Modules
Safety Modules
â„¢
NET B1
LINK B1
NET A1
LINK A1
NET A2
LINK A2
SPEED X1
LINK X1
OK
RUN
FORCE
FAN 1
SD
FAN 2
CompactLogix 5480
B1
A1
1
2
A2
5069-L46ERMW
CONTROLLER
UPS
MP
SA
R
B
F
R
B
F
DC INPUT
5069-IB16
DC OUTPUT
5069-OB16
ANALOG INPUT
5069-IY4
ANALOG OUTPUT
5069-OF8
DC INPUT
5069-IB16
IMPORTANT Compact 5000 I/O safety input modules cannot trigger events.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Allen-Bradley 5069-OBV8S and is the answer not in the manual?

Allen-Bradley 5069-OBV8S Specifications

General IconGeneral
BrandAllen-Bradley
Model5069-OBV8S
CategoryI/O Systems
LanguageEnglish

Related product manuals