Rockwell Automation Publication 5069-UM004A-EN-P - April 2019 259
Module Tag Definitions Appendix B
Input Tags
Table 78 describes the 5069-OB8 module input tags.
Output Tags
Table 79 describes the 5069-OB8 module output tags.
Table 78 - 5069-OB8 Module Input Tags
Name Size Definition Valid Values
RunMode BOOL Channel’s operating state • 0 = Idle
• 1 = Run Mode
ConnectionFaulted BOOL Indicates if a connection is running.
The module sets this tag to 0 when connected. If the
module is not connected, it changes the tag to 1.
• 0 = Connection running
• 1 = Connection not running
DiagnosticActive BOOL Indicates if any diagnostics are active or if the prognostics
threshold is reached.
• 0 = No diagnostics active
• 1 = One or more diagnostics are active or the
prognostics threshold is reached
DiagnosticSequenceCount SINT Increments for each time a distinct diagnostic condition is
detected, and when a distinct diagnostic condition
transitions from detected to not detected.
Set to zero by product reset or power cycle. Wraps from
255 (-1) to 1 skipping zero.
• -128…+127
The value of 0 is skipped except during module
power-up.
Ptxx.Data BOOL Indicates the current input value. • 0 = Off
• 1 = On
Ptxx.Fault BOOL Indicates that channel data is inaccurate and cannot be
trusted for use in the application.
For more information, see Module Data Quality Reporting
on page 71.
• 0 = Good data
• 1 = Bad data (Faulted)
If the tag is set to 1, you must troubleshoot the
module to correct the cause of the inaccuracy.
IMPORTANT: Once the condition that causes
the tag to change to 1 is removed, the tag
automatically resets to 0.
Ptxx.Uncertain BOOL Indicates that the channel data can be inaccurate but the
degree of inaccuracy is not known.
For more information, see
Module Data Quality Reporting
on page 71.
• 0 = Good data
• 1 = Uncertain data
If the tag is set to 1, you must troubleshoot the
module to correct the cause of the inaccuracy.
IMPORTANT: Once the condition that causes
the tag to change to 1 is removed, the tag
automatically resets to 0.
Ptxx.NoLoad BOOL Indicates that the signal wire has been disconnected from
one of its terminals or the RTB has been removed. Used
with Output channels.
• 0 = No fault
• 1 = Fault
Ptxx.ShortCircuit BOOL Indicates an output short circuit or overcurrent. • 0 = No short circuit
• 1 = Short circuit or overcurrent
Table 79 - 5069-OB8 Module Output Tags
Name Size Definition Valid Values
Ptxx.Data BOOL Indicates the current output value. • 0 = Off
• 1 = On

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Allen-Bradley 5069-OBV8S and is the answer not in the manual?

Allen-Bradley 5069-OBV8S Specifications

General IconGeneral
BrandAllen-Bradley
Model5069-OBV8S
CategoryI/O Systems
LanguageEnglish

Related product manuals