Installation/Wiring 1-27
The drive speed command can be obtained from a number of different sources. The source is
normally determined by P038
[Speed Reference]. However, when A051 - A054 [Digital Inx Sel] is
set to option 2, 4, 5, 6, 11, 12, 13, 14, 15 and the digital input is active, or if A132 is not set to
option 0, the speed reference commanded by P038
[Speed Reference] will be overridden. See
the chart below for the override priority.
Start and Speed Reference Control
Jog Input
Enabled and Active:
A051, A052, A053
or A054 = 2, 11, 12
No
Ye s
No
Drive Stopped
(Not Running)
Ye s
Drive will Start and Run
at Jog Speed.
Direction comes from
I/O Terminal 03 Dir/Run REV
or
Jog Forward/Jog Reverse command
Comm Select Input
Enabled and Active:
[Digital Inx Sel] = 6
No
Ye s
Start, Speed and Direction commands
come from RS485 (DSI) port.
0-10V Override
Enabled and Active:
[Digital Inx Sel] = 13
No
Ye s
Speed commands come from
0-10V or -10-10V.
Start and Direction
follows P036 [Start Source]
or
Bi-Polar input when enabled.
Speed commands come from 4-20mA.
Start and Direction
follows P036 [Start Source].
4-20mA Override
Enabled and Active:
[Digital Inx Sel] = 14
No
Ye s
P038 [Speed Reference]
= 4 or 5
No
Ye s
Run as specified by
P038 [Speed Reference].
Start and Direction commands come
from P036 [Start Source].
Run as specified by
A071-A077 [Preset Freq 1-7].
Start and Direction commands come
from P036 [Start Source].
A051/A052/A053
Preset Inputs Active
No
Ye s
Run as specified by
A132 [PID Ref Sel].
Start and Direction commands come
from P036 [Start Source].
PID Enabled:
A132 [PID Ref Sel]
0
No
Ye s
Run as specified by
P038 [Speed Reference].
Start and Direction commands come
from P036 [Start Source].
All Results
No change in control.
Run according to Priority Checklist.
Encoder Enabled
P038 = 8
or
A132 = 9
No
Ye s
Speed Commands as defined.
Encoder provides trim.
No change in direction control.
Encoder Type Selected:
A216 [Motor Fdbk Type]
0
No
Ye s
No change in control.

Table of Contents

Other manuals for Allen-Bradley PowerFlex 40P

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Allen-Bradley PowerFlex 40P and is the answer not in the manual?

Allen-Bradley PowerFlex 40P Specifications

General IconGeneral
BrandAllen-Bradley
ModelPowerFlex 40P
CategoryController
LanguageEnglish

Related product manuals