PID Set Up G-5
Analog PID Reference Signals
Parameters A110 [Anlg In 0-10V Lo] and A111 [Anlg In 0-10V Hi] are
used to scale or invert an analog PID Reference or PID Feedback.
Examples
Scale Function
For a 0-5 volt signal, the following parameter settings are used so that a 0
volt signal = 0% PID Reference and a 5 volt signal = 100% PID
Reference.
A110
[Anlg In 0-10V Lo] = 0.0%
A111 [Anlg In 0-10V Hi] = 50.0%
A132
[PID Ref Sel] = 2 “0-10V Input”
Invert Function
For a 4-20mA signal, the following parameter settings are used so that a
20mA signal = 0% PID Reference and a 4mA signal = 100% PID
Reference.
A112
[Anlg In4-20mA Lo] = 100.0%
A113
[Anlg In4-20mA Hi] = 0.0%
A132
[PID Ref Sel] = 3 “4-20mA Input”
0102030405060708090100
PID Reference (%)
Input Volts
2
4
6
8
10
12
0102030405060708090100
PID Reference (%)
4-20mA Input
4
8
12
16
20
24

Table of Contents

Other manuals for Allen-Bradley PowerFlex 40P

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Allen-Bradley PowerFlex 40P and is the answer not in the manual?

Allen-Bradley PowerFlex 40P Specifications

General IconGeneral
BrandAllen-Bradley
ModelPowerFlex 40P
CategoryController
LanguageEnglish

Related product manuals