3-30 Programming and Parameters
Advanced Program Group (continued)
A088 [Maximum Voltage] Related Parameter(s): b004, A085, A086, A087
Sets the highest voltage the drive will output.
Values Default: Drive Rated Volts
Min/Max: 20/Drive Rated Volts
Display: 1 VAC
A089 [Current Limit 1] Related Parameter(s): P033, A118
Maximum output current allowed before current limiting occurs.
Values Default: Drive Rated Amps × 1.5
Min/Max: 0.1/Drive Rated Amps × 1.8
Display: 0.1 Amps
A090 [Motor OL Select] Related Parameter(s): P032, P033
Drive provides Class 10 motor overload protection. Settings 0-2 select the derating factor for the I
2
t
overload function.
Options 0 “No Derate” (Default)
1 “Min Derate”
2 “Max Derate”